Technical Specification
NITROGEN GAS FLOW MEASUREMENT.
FLOW AND PROCESS FLUID SPECIFICATIONS: NITROGEN GAS, 38ºC,
SPECIFIC GRAVITY: 0.967. INLET PRESSURE 213.35 PSIG (15
KG/CM2), PIPE DIAMETER: 3". VOLUMETRIC FLOW: MINIMUM: 240
NM3/H (141.3 SCFM), NOMINAL: 960 NM3/H (565.03 SCFM), MAXIMUM: 1,200
NM3/H (706.29 SCFM). POWER SUPPLY: 24 VDC (LOOP POWERED).
THE TRANSMITTER MUST INCLUDE PRESSURE AND TEMPERATURE SENSORS IN
INTEGRAL FORM FOR MASS FLOW MEASUREMENT, ANALOG OUTPUT:
ACTIVE/PASSIVE (SELECTABLE) 4-20 MA, WITH HART PROTOCOL. HOUSING
FOR METER AND TRANSMITTER: NEMA 4X ALUMINUM, INCLUDES DISPLAY FOR
LOCAL INDICATION. CONNECTION TO PROCESS: FLANGED 300# ANSI B16.5.
INPUTS FOR ELECTRICAL CONNECTIONS: 1/2" NPT. ACCURACY: +/- 0.5%,
REPEATABILITY: +/- 0.1%, FM CLASS I DIV I APPROVAL.