Technical Specification
BCU 465W8P2C0D0010K2E1-/LM400WF3O0E1-
Burner control
On-site housing for controlling, igniting, and
monitoring pulse-controlled, modulating, or
stage-controlled gas burners. For continuous operation
with ionization monitoring or UV monitoring
using UV sensor UVD. Intermittent operation with
UV sensor UVS. Display of program status, unit
parameters, and flame signal.
Manual operation mode. Diagnosis and adjustment of
device parameters via optical interface and
PC software BCSoft. EU certified, FM and EAC
approved, certified for systems up to SIL 3
(corresponds to PL e).
Series: Version for extended air control
Mains voltage: 230 V~, 50/60 Hz
Ignition transformer: 8 kV, 20 mA, ED 33 %
Flange plate: M32
Valve monitoring system: None
High temperature operation: None
Input function: None
Pressure switch: Air pressure switch
Connection plugs: With spring force terminals
Packaging: Individual packaging
Energy supply: Via L1
Power module: Power module
Series: 400
Mains voltage: 230 V~, 50/60 Hz
Air actuator: With air valve control
Optional output: None
Energy supply: Via L1
I004 Flame monitoring: Ionization
I050 Contact function 80, 81/82: Fault signal
I051 Contact function 90, 91/92: Ready signal
I052 Contact function 95/96: Operating signal
Burner 1
I053 Contact function 95/97: Operating signal
Burner 1
I054 Contact function 85/86, 87: Air signal
I061 Function terminal 1: Start 1
I062 Function terminal 2: Reset
I063 Function terminal 3: Purge
I064 Function terminal 4: Air
I068 Function terminal 35: Safety chain
I069 Function terminal 36: Sensor 1
I070 Function terminal 37: Sensor 2
I071 Function terminal 38: Sensor 3
A001 Cut-off threshold burner 1: 4 micro A
A003 Foreign light check: In standby
A007 Startup attempts burner 1: 2
A093 Pre-ignition time tVZ: 0 s
A094 1st safety time startup: 3 s
A095 Flame stabilization time 1 tFS1: 0 s
A078 Burner application: Burner 1
A076 Function V5: Off
A009 Restart: Max. 5x for burner 1 in 15 min
A074 Combustion mode: Flame operation
A043 Afterrun: Off
A039 Afterrun time: 0 s
A016 Delayed low air pressure protection: On
A048 Air actuator control: Opens with gas stage 1
A129 Active cooling outputs: Air actuator
A034 Pre-purge time tPV: 7 s
A036 Air pre-ventilation time tVL: 0 s
A041 Running time selection: On, for approaching
positions for minimum/maximum capacity
A042 Running time: 4 s
A049 Air actuator on startup: Not externally controllable
A050 Air actuator on fault: Externally controllable
A019 Safety time operation: 1 s
A061 Minimum operating time tB: 4 s
A062 Minimum pause time tMP: 0 s
A067 Operating time manual operation: Limited to 5 min.
A087 Purge (bus): Via non-fail-safe bus
or terminal
A101 Function sensor 1: Air pressure switch purge
+ Stage 1 + Stage 2
A102 Function sensor 2: No function
A103 Function sensor 3: No function
A080 Fieldbus communication: Without address checking
A081 Kromschröder Safety Link: Off