Skip to main content
RX 9362035 RiLineX NH fuse disconnect switch

RX 9362035 Rittal United States Sales

If you are looking for a reliable supplier where you can purchase the RX 9362035 RiLineX NH fuse disconnect switch, you are in the right place. ONRION sells all product groups belonging to the Rittal brand in the United States market, with fast delivery times and competitive prices.

RX 9362035 RiLineX NH fuse disconnect switch
ProductRX 9362035
BrandRittal
HS Code85369095
CountryUnited States
Request a price
Delivery time: Determined at the time of quotation
VISA Mastercard Bank Transfer

Technical Specification

Execution
For 60 mm busbar systems
Benefit
Cover: lockable and sealable
Voltage testing through separate opening
Snap-on mounting up to 250 A and simple adjustment to busbar thickness 5/10 mm
Tool-free conversion of the outgoing cable
Parking position for simplified maintenance work
All variants also with electronic fuse monitoring
Material
Polyamide (PA 6)
Flammability according to UL 94
Contact paths: Electrolytic copper, silver-plated
Color
RAL 9005
RAL 35745
Scope of delivery
Including connection plug for electrical fuse monitoring
For rail systems with center distance
60 mm
Cable exit
top/bottom
Connection type (electrical)
Frame clamp
Fuse inserts
NH 00
NH 000
Rated insulation voltage Ui
1,000 V
Rated operating voltage
690 V AC
For NH size
00
Test basis
IEC/DIN EN 60 947-3
DIN EN 60 269-2 (fuse inserts)
Dimensions
Width: 106 mm
Height: 229.5 mm
Depth: 104.5 mm
Operating temperature range
-5 °C...35 °C
Storage temperature range
-25 °C...70 °C
Suitable for busbars
15 x 5/10 mm
20 x 5/10 mm
30 x 5/10 mm
Compatible with busbar system
RiLineX
RiLine60
Number of poles
3-pole
Usage category
AC-23B (400 V/100 A)
AC-22B (500 V/100 A)
AC-21B (690 V/100 A)
DC-22B (250 V/100 A)
Pollution degree
3
with electronic fuse monitoring (ESÜ)
Yes
Protection class IP according to IEC 60 529
IP 2XB
Fire load
16.6 MJ/m²
Connection of round conductors, fine-stranded without end sleeve
1.5 ‐ 95 mm²
Connection of round conductors, fine-stranded with end sleeve
1.5 ‐ 95 mm²
Maximum power loss
22 W
Power loss per fuse insert (max.)
12 W