Technical Specification
Ref: VA40/21.3-500GE 40 m/s 100 /p3 ZG7
Vortex VA flow sensor as in Drawing 7, sensor part
rectangular, width between corners 40 mm
Air/gas measurement range: 0.5... 40 m/s, actual flow velocity v
Working temperature range: -20... +100 °C
Maximum working pressure: up to 3 bar/300 kPa overpressure
Materials: stainless steel, ceramic, sensor housing 1.4581,
probe tube 1.4404, VITON, silicone free sensor
Installation length: 500 mm fixed length
Connection housing: AS80, L·W·H = 80 x 80 x 60 mm
Protection system: IP68 sensor connection housing IP65
with integrated probe guide part SFB 21,3 E-53/G 1½” ZG5
SF probe guide piece for connection to pipe or valve sleeves
ball with internal thread G 1½”. Fixing the probe using
clamping bushing.
Ball valves can only be closed after the probe is removed.
Installation length: approx. 53mm
Through hole: 21.3 mm
Material: Stainless steel
Seal: VITON, PTFE clamping bushing
Connection thread: external thread G 1½” thread length 22 mm
Calibration values v/t: 6 values
Calibration medium: air with integrated UVA transducer
Output flux: 4... 20 mA, max load 400 ohms
Output: open collector, max. 50mA, limit value v or pulse quantity,
max. 27 V DC
RS232 interface: to configure parameters with software
UCOM
Power supply: 24 V DC (20... 27 V DC)
Connection: GO 070 surface-mounted connector, for cable with